Phasor domain modeling of Type III wind turbine generator for protection studies

2015-09-30
Kauffmann, Thomas
Karaağaç, Ulaş
Kocar, Ilhan
Gras, Henry
Mahseredjian, Jean
Cetindag, Baki
Farantatos, Evangelos
The integration level of renewable energy resources has been continuously increasing in recent years introducing several technical challenges for utility and Independent System Operator (ISO) protection and planning engineers. One major challenge is related to the development of reliable models for system protection studies and accurate evaluation of their short circuit contributions. Converter interfaced wind turbines produce significantly different current waveform signatures compared to the traditional synchronous or asynchronous generators. This paper proposes a new phasor domain modeling approach for Type III wind turbines (WTs) with doubly-fed induction generators (DFIGs), that considers the impact of DFIG control.
IEEE Power and Energy Society General Meeting, PESGM 2015
Citation Formats
T. Kauffmann et al., “Phasor domain modeling of Type III wind turbine generator for protection studies,” Colorado, Amerika Birleşik Devletleri, 2015, vol. 2015-September, Accessed: 00, 2025. [Online]. Available: https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84956856086&origin=inward.