Çetinkaya, Süleyman
A repetitive control method for output voltage control of a three phase uninterruptible power supply (UPS) with isolation transformer is investigated. In the method voltage control loop is employed in the stationary dq frame. The controller eliminates the periodic errors on the output voltages due to inverter voltage nonlinearity and load disturbances. The controller design and implementation details are given. The controller is implemented on a 5-kVA UPS prototype which is constructed in laboratory. Linear and nonlinear loads for balanced and unbalanced load operating conditions are considered. The steady-state and dynamic performance of the control method are investigated in detail. The theory of the control strategy is verified by means of simulations and experiments.

Suggestions

Output voltage control of a four-leg inverter based three-phase ups by means of stationary frame resonant filter banks
Demirkutlu, Eyyüp; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2006)
A method for high performance output voltage control of a four-leg inverter based three-phase transformerless UPS is proposed. Voltage control loop is employed and the method employs stationary frame resonant filter controllers for the fundamental and harmonic frequency components. A capacitor current feedback loop provides active damping and enhances the output voltage dynamic performance. The controller design and implementation details are given. Linear and nonlinear loads for balanced and unbalanced loa...
Series active filter design, control, and implementation with a novel load voltage harmonic extraction method
Şentürk, Osman Selçuk; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2007)
Series Active Filters (SAF) are designed for harmonic isolation and load voltage regulation of single-phase and three-phase voltage harmonic source type nonlinear loads. The novel Absolute Value Method (AVM) for load voltage harmonic extraction is proposed and applied in the control algorithm of SAF. The SAF compensated systems are represented by simplified linear models such that SAF controller gains can be easily determined. Harmonic isolation and load voltage regulation performances of 2.5 kW single-phas...
Optimizing transient and filtering performance of a C-type 2nd harmonic power filter by the use of solid-state switches
Gerçek, Cem Özgür; Ertaş, Arif; Department of Electrical and Electronics Engineering (2007)
In this research work, the performance of a C-type, 2nd harmonic power filter is optimized by the use of a thyristor switched damping resistor. In the design of conventional C-type, 2nd harmonic filters; the resistance of permanently connected damping resistor is to be optimized for minimization of voltage stresses on filter elements arising from switchings in transient state and for maximization of filtering effectiveness in the steady-state. Transformer inrush current during energization of power transfor...
Performance of a dynamic voltage restorer for a practical situation
Oğuz, Gülçin; Ermiş, Muammer; Department of Electrical and Electronics Engineering (2004)
Among most severe power system disturbances those degrading power quality are voltage sags and transient interruptions. Even voltage sags lasting only a few tens of milliseconds are enough to bring entire production lines to standstill, causing considerable economic damage as well as endangering the production equipment. Therefore necessary measures have to be taken to protect sensitive loads which are susceptible to these voltage disturbances. Among the solution candidates such as, Uninterruptible Power Su...
Design and implementation of advanced pulse width modulation techniques and passive filters for voltage source inverter driven three-phase ac motors
Nebi, Onur Çetin; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2010)
Advanced pulse width modulation (PWM) techniques such as space vector PWM, active zero state PWM, discontinuous PWM, and near state PWM methods are used in three-phase AC motor drives for the purpose of obtaining low PWM current ripple, wide voltage linearity range, and reduced common mode voltage (CMV). In some applications, a filter is inserted between the inverter and the motor for the purpose of reducing the stresses in the motor. The motor current PWM ripple components, terminal voltage overshoots, sha...
Citation Formats
S. Çetinkaya, “Repetitive control of a three-phase uninterruptible power supply with isolation transformer,” M.S. - Master of Science, Middle East Technical University, 2006.