Output voltage control of a four-leg inverter based three-phase ups by means of stationary frame resonant filter banks

Download
2006
Demirkutlu, Eyyüp
A method for high performance output voltage control of a four-leg inverter based three-phase transformerless UPS is proposed. Voltage control loop is employed and the method employs stationary frame resonant filter controllers for the fundamental and harmonic frequency components. A capacitor current feedback loop provides active damping and enhances the output voltage dynamic performance. The controller design and implementation details are given. Linear and nonlinear loads for balanced and unbalanced load operating conditions are considered. The steadystate and dynamic performance of the UPS are investigated in detail. A scalar PWM method with implementation simplicity and high performance is proposed and implemented. The control and PWM methods are proven by means of theory, simulations, and experiments.

Suggestions

Repetitive control of a three-phase uninterruptible power supply with isolation transformer
Çetinkaya, Süleyman; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2006)
A repetitive control method for output voltage control of a three phase uninterruptible power supply (UPS) with isolation transformer is investigated. In the method voltage control loop is employed in the stationary dq frame. The controller eliminates the periodic errors on the output voltages due to inverter voltage nonlinearity and load disturbances. The controller design and implementation details are given. The controller is implemented on a 5-kVA UPS prototype which is constructed in laboratory. Linear...
Series active filter design, control, and implementation with a novel load voltage harmonic extraction method
Şentürk, Osman Selçuk; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2007)
Series Active Filters (SAF) are designed for harmonic isolation and load voltage regulation of single-phase and three-phase voltage harmonic source type nonlinear loads. The novel Absolute Value Method (AVM) for load voltage harmonic extraction is proposed and applied in the control algorithm of SAF. The SAF compensated systems are represented by simplified linear models such that SAF controller gains can be easily determined. Harmonic isolation and load voltage regulation performances of 2.5 kW single-phas...
Output voltage control of a four-leg inverter based three-phase UPS by means of stationary frame resonant filter banks
Demirkutlu, Eyyup; Cetinkaya, Sueleyman; Hava, Ahmet Masum (2007-05-05)
A method for high performance output voltage control of a four-leg inverter (FLI) based three-phase UPS is proposed. Stationary frame resonant filter bank based output voltage control loop, which is complemented by capacitor current feedback based active damping loop, is employed. Utilizing the zero-state partitioning variable, a generalized form of scalar PWM for the FLI is developed and the minimum loss discontinuous PWM method is derived. The controller and modulator design and implementation details for...
Design and implementation of advanced pulse width modulation techniques and passive filters for voltage source inverter driven three-phase ac motors
Nebi, Onur Çetin; Hava, Ahmet Masum; Department of Electrical and Electronics Engineering (2010)
Advanced pulse width modulation (PWM) techniques such as space vector PWM, active zero state PWM, discontinuous PWM, and near state PWM methods are used in three-phase AC motor drives for the purpose of obtaining low PWM current ripple, wide voltage linearity range, and reduced common mode voltage (CMV). In some applications, a filter is inserted between the inverter and the motor for the purpose of reducing the stresses in the motor. The motor current PWM ripple components, terminal voltage overshoots, sha...
Optimizing transient and filtering performance of a C-type 2nd harmonic power filter by the use of solid-state switches
Gerçek, Cem Özgür; Ertaş, Arif; Department of Electrical and Electronics Engineering (2007)
In this research work, the performance of a C-type, 2nd harmonic power filter is optimized by the use of a thyristor switched damping resistor. In the design of conventional C-type, 2nd harmonic filters; the resistance of permanently connected damping resistor is to be optimized for minimization of voltage stresses on filter elements arising from switchings in transient state and for maximization of filtering effectiveness in the steady-state. Transformer inrush current during energization of power transfor...
Citation Formats
E. Demirkutlu, “Output voltage control of a four-leg inverter based three-phase ups by means of stationary frame resonant filter banks,” M.S. - Master of Science, Middle East Technical University, 2006.